翻訳と辞書
Words near each other
・ Deltoidal icositetrahedron
・ Deltomerodes
・ Deltomerus
・ Delton
・ Delton AG
・ Delton Hall
・ Delton Stevano
・ Delton Township, Cottonwood County, Minnesota
・ Delton, Edmonton
・ Delton, Michigan
・ Delton, Wisconsin
・ Deltona High School
・ Deltona massacre
・ Delta-Valerolactone
・ Delta-Viniferin
Delta-wye transformer
・ Delta/Delta Heritage Air Park
・ Delta/Greely School District
・ Delta1 Canis Minoris
・ Delta1 Chamaeleontis
・ Delta1 Gruis
・ Delta1 Lyrae
・ Delta1-piperideine-2-carboxylate reductase
・ Delta11-fatty-acid desaturase
・ Delta12-fatty acid dehydrogenase
・ Delta12-fatty-acid desaturase
・ Delta14-sterol reductase
・ Delta2 Canis Minoris
・ Delta2 Chamaeleontis
・ Delta2 Gruis


Dictionary Lists
翻訳と辞書 辞書検索 [ 開発暫定版 ]
スポンサード リンク

Delta-wye transformer : ウィキペディア英語版
Delta-wye transformer

A delta-wye transformer is a type of three-phase electric power transformer design that employs delta-connected windings on its primary and wye/star connected windings on its secondary. A neutral wire can be provided on wye output side. It can be a single three-phase transformer, or built from three independent single-phase units. An equivalent term is delta-star transformer.
Delta-wye transformers are common in commercial, industrial, and high-density residential locations, to supply three-phase distribution systems.
An example would be a distribution transformer with a delta primary, running on three 11 kV phases with no neutral or earth required, and a star (or wye) secondary providing a 3-phase supply at 415 V, with the domestic voltage of 240 available between each phase and the earthed (grounded) neutral point.
The delta winding allows third-harmonic currents to circulate within the transformer, and prevents third-harmonic currents from flowing in the supply line. 〔 ''Electrical Transmission and Distribution Reference Book,Westinghouse Electric Corporation'', 1964, Chapter 5table 15〕 Delta connected windings are not common for higher transmission voltages (138 kV and above) owing to the higher cost of insulation compared with a wye connection. 〔 Fink and Beaty, ''Standard Handbook for Electrical Engineers 11th Edition'', Mc Graw Hill 1978, page 17-39 〕
Delta-wye transformers introduce a 30, 150, 270 or 330 degree phase shift.〔(【引用サイトリンク】url=http://212.175.131.171/IEC/iec60076-1%7Bed2.1%7Den_d.pdf#page=43 )〕 Thus they cannot be paralleled with wye-wye (or delta-delta) transformers. However, they can be paralleled with identical configurations and some different configurations of other delta-wye (or wye-delta with some attention) transformers.
==See also==

* Electric power distribution
* High-leg delta
* Mains power systems
* Motor soft starter